OutBack Power IMO FireRaptor Rapid Shutdown
The FireRaptor rapid shutdown system from IMO is a reliable, robust, simple
module level rapid shutdown system.
One FireRaptor OBFRS-01 unit is installed on each module, and is powered
by a two conductor cable system with its own connectors. The communications
cabling is hard wired, there is no wireless or power line communications in
this system that can fail due to interference from the charge control, inverter,
or externally. The operation is simple, if power is supplied to the units
at ~24 VDC they will turn on, if that power is interrupted, they will turn
off. The OBFRS-01 will also turn off if it senses an ambient temperature over
185°F (85°C) and turn back on when the temperature drops. If it senses
a temperature over 198°F (92°C) it will shutdown and require a manual
reset.
This system is compatible with any charge controls or inverters. Each OBFRS-01
unit comes with two MC4 module connectors on 5 inch pigtails, two string series
pigtails each at 71 inches with MC4 connectors, and two control wire pigtails
each at 71 inches with special connectors. The control wire is jacketed dual
conductor, and the connectors work for both connectors.
The OBFRS-SIGCAB1.8-F is a cable assembly with a connector on one end that
plugs into the first FireRaptor and is hard wired into the array j-box on
the other end. It adds another 71 inches in length to the lead on the first
FireRaptor.
The OBFRS-ESW1 is an Emergency Shutoff Switch that is used to turn the solar
array on and off. It comes with a 120 VAC to 24 VDC power supply capable of
powering up to 40 FireRaptors. If the 120 VAC power to the unit is off the
system will shutdown automatically. If the manual button is pushed the system
will shutdown. A 48 VDC to 24 VDC power supply can be substituted for the
AC to DC power supply that comes with the ESW1 for a more reliable manual
shutdown for systems with backup power. Emergency shutoff switches from other
systems can be substituted for the ESW1. For OutBack this can be the RSI,
and for MidNite the MNBirdhouse. Using the Aux contact closure in those switches
will shut off power to the FireRators on rapid shutdown, serving the same
purpose as the ESW1. This is helpful for systems with charge controls that
require a disconnect at the charge control end of the circuit because the
FireRaptor system will not serve that function directly.
If your modules will never exceed 40 VDC under any conditions, you can use
two modules in series for each OBFRS-01 unit (code requires a maximum of 80
VDC in the array on shutdown). The FireRaptor OBFRS-01 does not have any monitoring
or optimization.
See the attached wiring diagrams showing the various ways this system can
be set up. Contact an AEE Technical support person for assistance with your
design.