Home: EcoVantage Mobile Catalog: Batteries: UPS/Telecom:

Exide Marathon Front Terminal
Cat. No. Exide-MFT

Designed for durability in Telecommunications, and Electric Utility applications, the GNB FRONT Terminal MARATHONTM series provides high performance and reliability in long duration discharge applications. The location of the terminals on the front (vs. the top) of the battery greatly facilitates the installation and maintenance of the product when placed in a cabinet enclosure or on a standard relay rack tray. The MARATHONTM Front Terminal battery series highlights another example of GNB’s extensive experience and world wide leadership in VRLA technology.

“Designed in” Quality Manufacturing
Quality manufacturing processes for the MARATHONTM series batteries incorporate the industry’s most advanced technologies including: an automated helium leak detection system, a computer controlled “fill by weight” acid filler, and a temperature controlled water bath formation process. Each and every unit is capacity tested.

Front Terminal Valve Regulated
Lead Acid Battery for Standby
Power Applications
MARATHON FT Features:
  • Patented “Diamond Side-Wall” Design to maintain structural integrity in higher operating temperatures
  • Durable Flame Retardant Polypropylene Container and Cover compliant with UL94 V-0; 28% L.O.I.
  • Carry Handles for ease of installation
  • High-Compression Absorbent Glass Mat (AGM) Technology for greater than 99% recombination efficiency
  • Integrated Flash Arrestor ultrasonically welded into cover for secure and safe protection
  • 10 Year Design Life in float applications @ 25°C (77°F), 12 year @ 20°C (68°F)
  • Superior Lead-Tin-Calcium-Silver Positive Alloy helps to resist corrosion
  • Higher Vent Opening Pressure to avoid unnecessary gassing. One-way self resealing device tested and proven to maximize battery life
  • Front Accessible Copper Alloy, 6 mm, Female Terminals for low resistance, high integrity connections
  • “Easy On\Easy Off”Terminal Post Protector
  • Qualifications: IEC 896-2, UL Recognized Component, Eurobat 10-12 year High Performance
  • Footprint Ready for 19" and 23" Relay Rack Applications

Nominal Voltage:
12 Volts
Nominal Capacity:
90 Amp-Hours; 8 Hour Rate to 1.75 Volts Per Cell @ 25°C (77°F)
Alloy: Positive:
Lead, Tin, Calcium, and Silver
Negative:
Lead Calcium
Terminal:
Front Accessible, Heavy Duty Threaded (M6) copper alloy
Container:
I. Reinforced Flame Retardant Polypropylene UL94 V-0; 28% L.O.
Safety Vent:
One-way, self-resealing vent. Recessed design accommodates applications requiring central degassing.
Float Voltage:
2.25 VPC to 2.30 Volt Per Cell Range. Recommended 2.27 VPC @ 25°C (77°F)
Dimensions:
15.55" (395 mm) Length x 4.13" (105 mm) Width x 10.63” (270 mm) Height


MARATHONTM Specifications
Model
Number
Voltage Capacity (AH)
Nominal Dimensions
Nominal
Weight
8 Hr To 1.75
VCP @ 25oC
10 Hr To 1.80
VPC @ 20oC
    Inches    
Millimeters
A
B
C
A
B
C
lbs
kg
    M12V105FT
12
105
100
20.12
4.33
9.38
511
110
238
79
35.8
    M12V155FT
12
155
150
22.00
4.90
11.15
599
124
283
119
53.8
    M12V90FT 12 93.9
90.30
15.55
4.13
10.63
395
105
270
68.4
31
    M12V180FT 12 180
---
22.00
4.90
12.50
558.80
124.46
317.50
133
60.32