logo Mobile site   Catalog   EcoVantage Marine    Safety Works website
Home
EcoVantage Catalog
Policies
Mission
Marketing
Contact
Search:


Home: EcoVantage Catalog: Batteries: UPS/Telecom:

Fahrenheit HT145ET
Cat. No. HT145ET
Weight 102 lbs
$863.26

Fahrenheit Heat tolerant VRLA Battery

HT145ET
  • Helios™ Additive reduces float current up to 75% enhancing high temperature life
  • THT™ Plastic specifically formulated heat resistant plastic case and cover optimizes compression
  • Microcat® Catalyst lowers float current, mitigates thermal buildup and cell dryout
  • Exclusive IPF® Technology optimizes power capacity, cell consistency, and long-term reliability
  • TempX™ Alloy inhibits corrosion under the highest temperature extremes
  • Advanced AGM technology for superior power
  • Puncture resistant micro-porous glass mat separators extend life
  • Reinforced case resists bulging and meets safety requirements (UL 94 V-0)
  • Case & cover heat sealed and 100% tested to prevent leaks
  • Epoxy-sealed posts eliminate leaks
  • Flame arresting, low pressure, self-sealing valves are 100% factory tested
  • Computer-aided design and manufacturing control processes and standards to ensure quality products
  • All batteries meet or exceed IEEE recommended practices
  • Battery design and construction meet UL recognition requirements
SPECIFICATIONS
Nominal Voltage:  12-Volts
Rating: 140 Ampere-Hours @ 8 hr. rate

to 1.75 V.P.C.
Positive Plate:  >98% Pure lead with tin-calcium alloy
Negative Plate:  Pure lead, calcium alloy
Post Seal:  Epoxy-sealed
Terminal:  Front access, 1/4" – 20 threaded insert
Case/Cover:  Flame-retardant, polypropylene –

UL 94 V-0/>28% L.O.I
Catalyst:  Microcat®
Safety Vent:  Low positive pressure,

self-sealing w/ flame arrestor
Float Voltage:  2.25 V.P.C. ± 0.01 V.P.C. @ 77°F (25°C)

Range; (13.44V to 13.56V per battery)
Design life:  12 years in float applications @ 77°F (25°C)
Dimensions:  Length -17.36" (440.9 mm)

Width -6.90" (175.3 mm)

Height - 10.11" (256.7 mm)
Weight: 102 Ibs. (46.3 kg)

HT145ET Ratings @ 77°F (25°C)†
Volts per Cell
 (V.P.C.)
2 HR. 4 HR. 8 HR.20 HR
1.7554.639.417.57.8
†Ratings based on initial battery build.








EcoVantage Energy Inc© 
All rights reserved