Home: EcoVantage Catalog: Batteries: UPS/Telecom:
Exide Sprinter Next™ Cat. No. GNB-APCxxxFL Weight 52 lbs | |
Sprinter Next batteries incorporate advanced VRLA technology
designed for ultra high rate performance in critical UPS and power supply
applications.
SPRINTER NEXT™ BENEFITS
- The positive plates are designed for critical high rate UPS applications with a design life of 10 years at 25ºC (77ºF)
- Standard ABS plastic jar and covers meet UL94 V-0 flame retardant requirements
- Muliticell design for faster installation in cabinets or on racks. A separate battery room is not necessary
- Heavy duty copper alloy terminals for ease of assembly and reduced maintenance
- 100% initial capacity
- UL recognized
- IEC60896 – 21 & 22, third party tested and compliant
- IATA approved for AIR freight to be shipped as non-spillable
Model
Number
|
Nominal Voltage (V)
|
Rated Capacity
|
Nominal Dimensions
(in)
|
Nominal Weight (lbs) |
15 min. WPC
1.67 VPC
|
20 HR (Ah)
1.80 VPC
|
L
|
W
|
H
|
Terminal Height
|
S12V325FL
|
12
|
324.9
|
82
|
10.24
|
6.61
|
8.19
|
8.31
|
52.9
|
S12V370FL
|
12
|
370.3
|
95
|
12.05
|
6.61
|
8.15
|
8.27
|
61.7
|
S12V539FL
|
12
|
539.0
|
155
|
13.19
|
6.77
|
10.83
|
10.95
|
93.5
|
|
Internal
Resistance
(milliohms)
|
Short Circuit
Current (Amps)
|
Terminal Type
|
S12V325FL
|
4.5
|
1640
|
T6
|
S12V370FL
|
4.0
|
1900
|
T6
|
S12V539FL
|
3.1
|
3100
|
T8
|
PRODUCT DESCRIPTION
Positive Plate | Lead-calcium grids minimize corrosion & prolong life |
Negative Plate | Balanced lead-calcium grids optimize recombination efficiency |
AGM Separator | Mechanically strong, low electrical resistance, micro porous
glass fiber which completely absorbs the electrolyte into its structure |
Terminal Post | Threaded copper alloy terminals for maximum conductivity |
Venting Valve | EPDM Rubber 0.44 ~2.18 PSI resealing pressure. Releasing at 1.45~5.08 PSI. |
Container | ABS -Flame Retardant Containers to UL94V-0 is standard. |
|
|
|