Exeltech XP1100 and XP2000 Sine Wave Inverter Cat. No. ELX-XP1100 Weight 40 lbs
Made in America, EXELTECH XP SERIES
INVERTERS are the most affordable, reliable, lightweight and best
regulated, true sine wave inverters available. The XP SERIES inverter
will operate any AC load anywhere. Ultra lightweight, yet rugged enough
for the most extreme mobile environments, and are UL listed to 1950 for
telecom applications. The XP SERIES is available in 100Vac, 120Vac, or
230Vac in 50Hz, 60Hz or 400Hz and suited for multiple applications,
worldwide.
- True Sine Wave
- 1100 Watts
- 12 Vdc to 108 Vdc Input
- Rack Mount Optional
- Remote Switching
- 21.5 Years MTBF
DC INPUTS (12 VDC - 108 VDC): a 6' non-terminated, two conductor
power cord is provided. Insulation on the negative (-)conductor is
black and insulation on the positive (+) conductor is red.
AC OUTPUTS:one
NEMA-15 outlet (standard wall receptacle) is located on the Front Panel.
LOW BATT /
THERM BUZZER ; produces an audible alarm if DC input voltage
falls to a level within 2% to 4% of the low limit of inverter, or, if
there is an over temperature condition.
OVER VOLTAGE
PROTECTION: If input voltage to the inverter exceeds set limits,
the inverter will immediately and without warning shut off. When input
voltage returns to normal range, the inverter will immediately restart.
Since high over voltages tend to have very fast edges, the inverter
must shut down quickly to protect itself. This kind of fault usually
occurs if the battery is suddenly disconnected from the system and the
battery charger continues to supply current.
UNDER
VOLTAGE PROTECTION: When battery voltage falls to within 2% to
4% of low line voltage, the LOW BATT / THERM buzzer will sound. If the
condition continues without reducing load to the inverter or adding
charge to the battery, the inverter will shut off. When voltage rises
to approximately 95% of nominal battery voltage, the inverter will turn
back on and the alarm condition will clear. The inverter can be
manually reset by cycling the on/off switch. This will reset the
protection circuitry and turn the inverter on at any voltage above
minimum voltage.
Output Power
Continuous Power
Surge Power
No Load Power
Output Voltage
Output Current
Weight LBS.
1100 Watt**
2200 Watts
20 Watts*
100 +/- 6%
11.0
10
1100 Watt**
2200 Watts
20 Watts*
120 +/- 6%
9.5
10
1100 Watt**
2200 Watts
20 Watts*
230 +/- 6%
4.8
10
Input Power
Model Voltage
Minimum (Typical)**
System (Typical)
Maximum (Typical)**
Typical Efficiency @ Full Power
Peak Efficiency @ 1/3 Power
12Vdc
10.4/10.6Vdc*
13.8Vdc
16.5Vdc
85%
87%
24Vdc
19/21Vdc*
27.6Vdc
33Vdc
87%
89%
32Vdc
26.5/28Vdc*
36.8Vdc
44Vdc
88%
90%
48Vdc
41.5/42.1Vdc*
55.2Vdc
62Vdc
87%
89%
66Vdc
57.5/58.5Vdc*
75.9Vdc
91.1Vdc
88%
90%
108Vdc
94/95Vdc*
125Vdc
149Vdc
87%
90%
*Indicates typical cut-off voltage/warning
buzzer voltage